2016 Winnipeg distribution system water quality test results
The Winnipeg distribution system is the last location where we add chlorine to the water - at the outlet from each of the three pumping stations. The other locations are at the Shoal Lake intake on a periodic basis and at the Water Treatment Plant.
Our Operating Licence requires that we maintain a minimum free chlorine residual of 0.1 milligrams per litre throughout the distribution system.
Testing
Winnipeg water is intensively monitored on a routine basis at Shoal Lake, before it enters the Water Treatment Plant and after the water has passed through the treatment processes to ensure that the water is safe and that regulatory requirements are met. Because water quality is so important, our level of monitoring and sampling exceeds Provincial regulatory requirements.
- Equipment is used to continuously monitor chlorine levels at the pumping stations and we test the chlorine levels at 60 locations throughout the distribution system on a weekly basis.
- Microbiological samples are taken weekly at 60 locations throughout the distribution system. Tests are conducted for Escherichia coli and total coliform bacteria according to Provincial regulations, and we also test for Heterotrophic plate count which is not required under Provincial regulations, but can be useful to identify potential problem areas within the distribution system.
We also test Winnipeg distribution system water for:
- routine water chemistry
- metals
- disinfection by-products
We use these test results to monitor water quality changes within the distribution system and the quality of water delivered to customers. We also respond to customer inquiries and complaints about water quality. Contact us for more information.
Test results are from January 1 to December 31, 2016
What is being measured | How it's measured | Guideline or regulation | Winnipeg average | Winnipeg range | Comments |
Miscellaneous | |||||
Carbon, Dissolved Organic | parts per million | no guideline | 2.8 | 2.5 to 3.4 | - |
Carbon, Total Organic | parts per million | no guideline | 2.7 | 2.4 to 3.2 | - |
Chlorine, Free | parts per million | no guideline | 0.83 | <0.02 to 1.72 | - |
Chlorine, Total | parts per million | no guideline | 1.04 | 0.06 to 1.87 | - |
Colour, True | TCU | no more than 15 * | 1.2 | 0.5 to <5.0 | Meets the guideline |
Conductivity | microsiemens per centimetre | no guideline | 306 | 290 to 323 | Another measure of dissolved solids |
Langelier Index (4 C) | units | no guideline | -0.94 | -0.89 to -1.00 | - |
Langelier Index (60 C) | units | no guideline | -0.18 | -0.12 to -0.27 | - |
Odour | units | inoffensive | 11 | 8 to 20 | Meets the guideline |
Oxygen, Dissolved | parts per million | no guideline | 12.5 | 8.3 to 15.6 | - |
pH | units | between 6.5 and 8.5 | 7.45 | 7.19 to 7.81 | Meets the guideline |
Solids, Total Dissolved | parts per million | no more than 500 * | 182 | 154 to 205 | Meets the guideline |
Temperature | degrees Celcius | no more than 15 * | 11.3 | 1.1 to 23.9 | Does not always meet the guideline |
Turbidity (clearness) | NTU | no guideline | 0.32 | 0.08 to 20.6 | - |
UV Transmittance, Unfiltered | percent transmissivity | no guideline | 93.4 | 91.2 to 96.6 | - |
Anions and Nutrients | |||||
Alkalinity, Total | parts per million as calcium carbonate | no guideline | 66 | 58 to 78 | - |
Alkalinity, Bicarbonate | parts per million | no guideline | 79 | 75 to 83 | - |
Alkalinity, Carbonate | parts per million | no guideline | <0.60 | <0.60 to <0.60 | - |
Alkalinity, Hydroxide | parts per million | no guideline | <0.34 | <0.34 to <0.34 | - |
Hardness, Total | parts per million as calcium carbonate | no guideline | 81 | 74 to 90 | - |
Ammonia | parts per million | no guideline | <0.010 | <0.010 to 0.014 | - |
Bromate | parts per million | no more than 0.01 | <0.0050 | <0.0050 to <0.0050 | Meets the guideline |
Bromide | parts per million | no guideline | <0.10 | <0.10 to <0.10 | - |
Chloride | parts per million | no more than 250 * | 22 | 19 to 27 | Meets the guideline |
Fluoride | parts per million | no more than 1.5 | 0.69 | 0.54 to 0.86 | Meets the guideline |
Nitrate Nitrogen | parts per million | no more than 10 | 0.0265 | 0.0077 to 0.0517 | Meets the guideline |
Nitrite | parts per million | no guideline | <0.0010 | <0.0010 to 0.0014 | - |
Perchlorate | parts per billion | no guideline | <0.2 | <0.2 to <0.2 | - |
Phosphate, Soluble | parts per million as phosphate | no guideline | 1.93 | 1.69 to 2.17 | Added for Lead Control Program |
Phosphorus,Total | parts per million | no guideline | 0.64 | 0.60 to 0.70 | Phosphorus can contribute to algae growth |
Sulphate | parts per million | no more than 500 * | 52 | 43 to 64 | Meets the guideline |
Bacteria | |||||
Escherichia Coli | MPN per 100 mL | less than one bacteria detectable per 100 mL | <1 | <1 to <1 | Meets the guideline |
Total Coliforms | MPN per 100 mL | less than one bacteria detectable per 100 mL | <1 | <1 to 2 | All resamples were negative and met the operating licence requirements |
Heterotrophic Plate Count | CFU per mL | no guideline | 2 | <1 to >300 | - |
Disinfection By-Products | |||||
Aldehydes | parts per billion | no guideline | 15.2 | 1.9 to 25.3 | - |
Bromodichloromethane | parts per billion | no guideline | 2.5 | <1.0 to 5.3 | - |
Haloacetic acids | parts per billion | no more than 80 | 25 | 8 to 39 | Meets the guideline |
Trihalomethanes | parts per billion | no more than 100 | 26 | 4 to 56 | Meets the guideline |
Total Metals | |||||
Aluminum | parts per million | no guideline | 0.0175 | 0.0042 to 0.1313 | - |
Antimony | parts per million | no more than 0.006 | 0.0003 | <0.0002 to 0.0006 | Meets the guideline |
Arsenic | parts per million | no more than 0.010 | 0.0006 | <0.0003 to 0.0008 | Meets the guideline |
Barium | parts per million | no more than 1 | 0.0153 | 0.0149 to 0.0160 | Meets the guideline |
Beryllium | parts per million | no guideline | <0.00020 | <0.00020 to <0.00020 | - |
Bismuth | parts per million | no guideline | <0.00020 | <0.00020 to <0.00020 | - |
Boron | parts per million | no more than 5 | 0.0100 | <0.0005 to 0.0421 | Meets the guideline |
Cadmium | parts per million | no more than 0.005 | 0.00020 | <0.00001 to <0.00040 | Meets the guideline |
Calcium | parts per million | no guideline | 21.0 | 16.1 to 28.9 | Contributes to hardness |
Cesium | parts per million | no guideline | <0.00010 | <0.00010 to 0.00017 | - |
Chromium VI | parts per billion | no guideline | 2 | <1 to <10 | - |
Chromium | parts per million | no more than 0.05 | 0.0008 | <0.0007 to 0.0026 | Meets the guideline |
Cobalt | parts per million | no guideline | <0.00020 | <0.00020 to 0.00028 | - |
Copper | parts per million | no more than 1.0 * | 0.0284 | 0.0019 to 0.1010 | Meets the guideline |
Iron | parts per million | no more than 0.3 * | 0.053 | <0.008 to 0.640 | Does not always meet the guideline |
Lead | parts per million | no more than 0.010 | 0.00021 | <0.00009 to 0.00092 | Meets the guideline |
Lithium | parts per million | no guideline | 0.0026 | 0.0023 to 0.0029 | - |
Magnesium | parts per million | no guideline | 5.95 | 4.31 to 7.48 | Contributes to hardness |
Manganese | parts per million | no more than 0.05 * | 0.0252 | 0.0103 to 0.1925 | Does not always meet the guideline |
Mercury | parts per trillion | no more than 1000 | 0.8 | <0.5 to 15.0 | Meets the guideline |
Molybdenum | parts per million | no guideline | <0.00020 | <0.00020 to <0.00020 | - |
Nickel | parts per million | no guideline | 0.0025 | 0.0012 to 0.0061 | - |
Potassium | parts per million | no guideline | 1.18 | 0.89 to 1.48 | - |
Rubidium | parts per million | no guideline | 0.00179 | 0.00164 to 0.00191 | - |
Selenium | parts per million | no more than 0.05 | <0.0010 | <0.0010 to <0.0010 | Meets the guideline |
Silicon | parts per million | no guideline | 2.45 | 1.16 to 3.46 | - |
Silver | parts per million | no guideline | <0.00010 | <0.00010 to <0.00010 | - |
Sodium | parts per million | no more than 200 * | 31.6 | 23.4 to 40.6 | Meets the guideline |
Strontium | parts per million | no guideline | 0.0396 | 0.0363 to 0.0426 | - |
Tellurium | parts per million | no guideline | <0.00020 | <0.00020 to <0.00020 | - |
Thallium | parts per million | no guideline | <0.00010 | <0.00010 to <0.00010 | - |
Thorium | parts per million | no guideline | <0.00010 | <0.00010 to <0.00010 | - |
Tin | parts per million | no guideline | 0.00022 | <0.00020 to 0.00058 | - |
Titanium | parts per million | no guideline | <0.00050 | <0.00050 to <0.00050 | - |
Tungsten | parts per million | no guideline | <0.00010 | <0.00010 to <0.00010 | - |
Uranium | parts per million | no more than 0.02 | 0.0002 | <0.0001 to <0.0005 | Meets the guideline |
Vanadium | parts per million | no guideline | <0.00020 | <0.00020 to <0.00020 | - |
Zinc | parts per million | no more than 5.0 * | 0.0047 | <0.0005 to 0.0362 | Meets the guideline |
Zirconium | parts per million | no guideline | 0.0004 | <0.0004 to 0.0020 | - |
Note: Where value is expressed as less than (<), the value is halved and used in the calculations, where value is expressed as greater than (>), the value is used in the calculations
* Aesthetic Objective: These guidelines have an objective and not a maximum acceptable limit. These parameters should not impact the safety of the water to drink and there is no anticipated health risk for short-term exposures.
Guidelines from ‘Summary of Guidelines for Canadian Drinking Water Quality' by Health Canada, October 2014
Data reported was collected from a combination of MacLean, Hurst, and McPhillips Pumping Station Discharges, 57 distribution system locations, and/or Branch I at McPhillips and Branch II at Hurst.
Bacterial testing
What is being measured | Requirement | Our test results | Comments |
Number of total coliform bacteria tests in year | 2028 samples/year | 3,141 | More testing than required by the operating licence |
Number of times that total coliform bacteria show up in a test | less than one bacteria detectable per 100 mL | 0.19% (6 positive tests) |
All resamples were negative and met the operating licence requirements |
Number of Escherichia coli bacteria tests in year | 2028 samples/year | 3,141 | More testing than required by the operating licence |
Number of times that Escherichia coli bacteria show up in a test | less than one bacteria detectable per 100 mL | 0.00% (0 positive tests) |
|
Number of heterotrophic (bacteria) plate count (HPC) tests done | no guideline | 3,135 | Heterotrophic plate count testing is not required under the operating licence |
Requirements from City of Winnipeg Operating Licence PWS-09-412-01
Data reported was collected from 57 distribution system locations and MacLean, Hurst, and McPhillips Pumping Station Discharges